Module-PS48A

48 Volt Power supply with a 200 Mhz CPU to monitor:  Temperature, Voltage in, Voltage out, How much in % is the PS loaded, total uptime hours, Amount of restarts, and many more. They are all avalible in variables for your SCADA/DCS or for your tablet/Smarty Phone. Support Hot Swap & Redundancy.
In redundancy it is Load Sharing
Two (or more) can be inserted next to each other, to provide power supply redundancy. The two power supplies will do simple load sharing. If the total load is 100%, one PSU will deliver e.g. 50%, and the second 50%.
If more than 100% (1.2 A) is needed, a new power supply segment is needed

30-60 VDC Power Supply Module

Customers in different industries that use our IO modules. 

Netweok Rail  

Thames Water 

BP

UK power networks

Module Input power.

Input supply voltage:

30..60  VDC ( Vin )

 

Input Power Consumption:

24W ±%5

Module Output power.

Output voltage:

12 VDC +- 10% for I/O modules and electronics.

 

Output voltage:

max 1.2 A continuous for I/O modules.

max 1.6 A overload current limit / short circuit protection.

In case of an overload or short circuit, module will turn off and retry after approximately 10 ms.    

Module input voltage, current, and output voltage, current is monitored by CPU, and reported to RTU at regular intervals.

Ambient Temperature range:

Operating:                             -20°C to +75°C

Storage:                                 -40°C to +85°C

Power supply redundancy:

Two (or more) power supplies can be inserted next to each other, to provide power supply redundancy. The two power supplies will do simple load sharing. If the total load is 100%, one PSU will deliver e.g. 60%, and the second 40%.

Note: This is for redundancy only. If more than 100% (1.2 A) is needed, a new power supply segment is needed.     

Customers in different industries that use our IO modules. 

Netweok Rail  

Thames Water 

BP

UK power networks