NJORD-VAR

Run the Whole Pump Station from One Platform

NJORD-VAR combines dedicated pump control with a modern industrial RTU. One platform runs the station logic, the local HMI, the data logging and the link to SCADA, for water, wastewater, reservoir, well and industrial pumping applications.

Three operating modes · Protection in every mode · SCADA ready · Built on the RTU32M

One Screen, the Whole Station

The overview screen carries the current station level, the status of every pump, the operating mode and any active alarms. An operator should not have to move between screens to understand the condition of the station.

On the overview screen

Configured, Not Re-engineered

The same platform suits a two pump lift station and a large reservoir because the behaviour is set in parameters rather than rewritten in code. Site differences are handled on the configuration screen.

Set per site

Pumps Follow the Level

As the level reaches the first configured start point the duty pump runs. If the level keeps rising, each further start level brings in the next available pump, up to the maximum number permitted to run at once. When the level falls, pumps stop in the configured sequence.

How staging works

A Faulted Pump Does Not Stop the Station

Protection is part of the controller rather than something layered on top, and it stays in force in every operating mode. Changing between Auto, Manual and Remote does not bypass it.

Protection in force

What Happened, Where, and When

At an unmanned station, knowing that something went wrong is not enough. NJORD-VAR keeps an event history so maintenance and operations can reconstruct the sequence instead of guessing at it.

Recorded per pump

put it on your next station

Pump Controller and Station RTU in One

NJORD-VAR is built on the Brodersen RTU32M, so the same device that runs the pumps also talks to the control centre — removing the separate layer of telemetry equipment a dedicated pump controller would normally need beside it. For new stations, and for retrofit where an older dedicated controller is reaching the end of its life.

Three operating modes · Protection in every mode · SCADA ready · Built on the RTU32M

What You Can Configure

Every value below is set on the station configuration screen. No two sites need the same numbers.

SettingWhat it controls
Number of pumps at this siteHow many pumps the station logic manages
Maximum number of pumps allowed to runCeiling on how many run at the same time, whatever the level does
Start levels, high level, low level cut offThe level thresholds that stage pumps in and out
Start delayDelay before a pump starts once its level point is reached
Stop delayDelay before a pump stops as the level falls
Maximum runtime allowedLongest a single pump may run before the controller acts
Anti short cycle timeMinimum gap between starts, to stop rapid cycling
Dry run delayHow long a dry run condition must persist before it is treated as a fault
Run feedback delayHow long to wait for run confirmation before raising a feedback failure
Pump fault timerHow long a fault condition must hold before the pump is locked out
Priority modeSelects how the next pump to run is chosen
Pump rating, runtime and start countersSet per pump; counters can be reset after maintenance

Where It Is Used

Application What NJORD-VAR handles
Water and wastewater lift stations Level based staging, duty rotation, dry run and overload protection, SCADA reporting
Industrial pump stations Process pumping with runtime balancing and local HMI supervision
Reservoirs and wells Level control with historical trend and flow information
Retrofit of an existing station Replaces a standalone pump controller, the RTU, the local HMI and the data logger with one platform

Newsletter

Download the NJORD-VAR brochure

Your download will start as soon as you submit.

This field is for validation purposes and should be left unchanged.